POK, full catalogue English

375 POK SAS - 18 Cours Antoine Lavoisier - 10400 Nogent-sur-Seine - FRANCE Phone: +33 (0)3 37 49 53 - 000 - Email: export@pok-fire.com - Web: www.pok-fire.com Turbo-pumps Outlet turbine Inlet turbine Outlet evacuation Drain control Anchor ring Inlet turbine Outlet turbine Outlet evacuation Dimensions (mm) Weight (kg) Ref. 2" BSP male 2,5" BSP male 2,5" BSP male 302 x 301 x 260 10,4 45034 2,5" BSP male 2,5" BSP male 2,5" BSP male 302 x 350 x 260 10,6 45037 DSP DN65 DSP DN65 DSP DN65 304 x 370 x 301 11,4 45040 DSP DN65 with lock DSP DN65 with lock DSP DN65 with lock 307 x 368 x 347 12,1 45043 Storz B/75 Storz B/75 Storz B/75 324 x 378 x 298 12 44015 Exhaust turbo-pump 54m 3 /h With a flow rate of 650 Lpm at 8 bar at the turbine outlet, these turbo pump models achieve a suction rate of 900 Lpm, or 54m3/h. The turbo pump transfers fluid between two separate points by exploiting the hydraulic energy of a pressurised working fluid. The latter is injected at the turbine inlet, causing it to rotate and, through mechanical coupling, driving the pump impeller. This impeller creates a vacuum at the suction point, allowing the fluid to be transferred to be drawn in, which is then discharged to the destination point. One of the major advantages of this device is the physical separation between the drive fluid (clean) and the pumped fluid (potentially contaminated), thus avoiding any cross-contamination. Suction